Permit Number: TC-COM-0125-00209
Parcel: 11628001L

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0125-00209
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2025 Site Zoning Standard APPROVED
02/25/2025 Water - PDSD Standard APPROVED
02/28/2025 Site Engineering Standard NOT REQUIRED
02/26/2025 Site Landscape Standard NOT REQUIRED
02/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/26/2025 Commercial Building Standard REQUIRES RESUBMIT February 13, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT MARKETPLACE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00209
Stantec Project Number: 185215066
Stantec File Number: TUC-25-023

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 I-B 3,600 N/A Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors and field welding.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please provide a City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet A0.0

1. Please provide updated occupant load calculations for the proposed use. [Ref. IBC 2018 Sec. 1004.5]

Sheet A2.0

1. Please indicate the location of all dining and drinking areas along with a minimum 5% of these areas as being accessible. [Ref. IBC 2018 Sec. 1108.2.9.1]

2. Please provide the location of the accessible portion of the point of sale/service counter. [Ref. IBC 2018 Sec. 904.1]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E3.0

1. Please provide updated short-circuit calculations for the relocated panels. [Ref. NEC 2017 Art. 110.10]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
02/26/2025 Commercial Electrical Standard REQUIRES RESUBMIT February 13, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT MARKETPLACE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00209
Stantec Project Number: 185215066
Stantec File Number: TUC-25-023

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 I-B 3,600 N/A Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors and field welding.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please provide a City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet A0.0

1. Please provide updated occupant load calculations for the proposed use. [Ref. IBC 2018 Sec. 1004.5]

Sheet A2.0

1. Please indicate the location of all dining and drinking areas along with a minimum 5% of these areas as being accessible. [Ref. IBC 2018 Sec. 1108.2.9.1]

2. Please provide the location of the accessible portion of the point of sale/service counter. [Ref. IBC 2018 Sec. 904.1]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E3.0

1. Please provide updated short-circuit calculations for the relocated panels. [Ref. NEC 2017 Art. 110.10]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
02/26/2025 Commercial Mechanical Standard REQUIRES RESUBMIT February 13, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT MARKETPLACE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00209
Stantec Project Number: 185215066
Stantec File Number: TUC-25-023

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 I-B 3,600 N/A Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors and field welding.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please provide a City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet A0.0

1. Please provide updated occupant load calculations for the proposed use. [Ref. IBC 2018 Sec. 1004.5]

Sheet A2.0

1. Please indicate the location of all dining and drinking areas along with a minimum 5% of these areas as being accessible. [Ref. IBC 2018 Sec. 1108.2.9.1]

2. Please provide the location of the accessible portion of the point of sale/service counter. [Ref. IBC 2018 Sec. 904.1]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E3.0

1. Please provide updated short-circuit calculations for the relocated panels. [Ref. NEC 2017 Art. 110.10]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
02/26/2025 Commercial Plumbing Standard REQUIRES RESUBMIT February 13, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT MARKETPLACE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00209
Stantec Project Number: 185215066
Stantec File Number: TUC-25-023

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 I-B 3,600 N/A Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors and field welding.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please provide a City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet A0.0

1. Please provide updated occupant load calculations for the proposed use. [Ref. IBC 2018 Sec. 1004.5]

Sheet A2.0

1. Please indicate the location of all dining and drinking areas along with a minimum 5% of these areas as being accessible. [Ref. IBC 2018 Sec. 1108.2.9.1]

2. Please provide the location of the accessible portion of the point of sale/service counter. [Ref. IBC 2018 Sec. 904.1]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E3.0

1. Please provide updated short-circuit calculations for the relocated panels. [Ref. NEC 2017 Art. 110.10]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
02/06/2025 Fire New Construction Standard REVIEW COMPLETED Alterations to the Fire Alarm or Fire Sprinklers Systems will require a separate submittal.