Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0125-00209
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/25/2025 | Site Zoning Standard | APPROVED | |||
02/25/2025 | Water - PDSD Standard | APPROVED | |||
02/28/2025 | Site Engineering Standard | NOT REQUIRED | |||
02/26/2025 | Site Landscape Standard | NOT REQUIRED | |||
02/28/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
02/26/2025 | Commercial Building Standard | REQUIRES RESUBMIT | February 13, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/ Daren Sadowsky 2552 N. Alvernon Way Tucson, Arizona 85712 Re: STARR PASS MARRIOTT MARKETPLACE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0125-00209 Stantec Project Number: 185215066 Stantec File Number: TUC-25-023 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-2 I-B 3,600 N/A Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Epoxy and expansion anchors and field welding. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Please provide a City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet A0.0 1. Please provide updated occupant load calculations for the proposed use. [Ref. IBC 2018 Sec. 1004.5] Sheet A2.0 1. Please indicate the location of all dining and drinking areas along with a minimum 5% of these areas as being accessible. [Ref. IBC 2018 Sec. 1108.2.9.1] 2. Please provide the location of the accessible portion of the point of sale/service counter. [Ref. IBC 2018 Sec. 904.1] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS Sheet E3.0 1. Please provide updated short-circuit calculations for the relocated panels. [Ref. NEC 2017 Art. 110.10] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
02/26/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | February 13, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/ Daren Sadowsky 2552 N. Alvernon Way Tucson, Arizona 85712 Re: STARR PASS MARRIOTT MARKETPLACE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0125-00209 Stantec Project Number: 185215066 Stantec File Number: TUC-25-023 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-2 I-B 3,600 N/A Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Epoxy and expansion anchors and field welding. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Please provide a City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet A0.0 1. Please provide updated occupant load calculations for the proposed use. [Ref. IBC 2018 Sec. 1004.5] Sheet A2.0 1. Please indicate the location of all dining and drinking areas along with a minimum 5% of these areas as being accessible. [Ref. IBC 2018 Sec. 1108.2.9.1] 2. Please provide the location of the accessible portion of the point of sale/service counter. [Ref. IBC 2018 Sec. 904.1] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS Sheet E3.0 1. Please provide updated short-circuit calculations for the relocated panels. [Ref. NEC 2017 Art. 110.10] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
02/26/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | February 13, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/ Daren Sadowsky 2552 N. Alvernon Way Tucson, Arizona 85712 Re: STARR PASS MARRIOTT MARKETPLACE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0125-00209 Stantec Project Number: 185215066 Stantec File Number: TUC-25-023 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-2 I-B 3,600 N/A Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Epoxy and expansion anchors and field welding. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Please provide a City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet A0.0 1. Please provide updated occupant load calculations for the proposed use. [Ref. IBC 2018 Sec. 1004.5] Sheet A2.0 1. Please indicate the location of all dining and drinking areas along with a minimum 5% of these areas as being accessible. [Ref. IBC 2018 Sec. 1108.2.9.1] 2. Please provide the location of the accessible portion of the point of sale/service counter. [Ref. IBC 2018 Sec. 904.1] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS Sheet E3.0 1. Please provide updated short-circuit calculations for the relocated panels. [Ref. NEC 2017 Art. 110.10] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
02/26/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | February 13, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/ Daren Sadowsky 2552 N. Alvernon Way Tucson, Arizona 85712 Re: STARR PASS MARRIOTT MARKETPLACE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0125-00209 Stantec Project Number: 185215066 Stantec File Number: TUC-25-023 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-2 I-B 3,600 N/A Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Epoxy and expansion anchors and field welding. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Please provide a City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet A0.0 1. Please provide updated occupant load calculations for the proposed use. [Ref. IBC 2018 Sec. 1004.5] Sheet A2.0 1. Please indicate the location of all dining and drinking areas along with a minimum 5% of these areas as being accessible. [Ref. IBC 2018 Sec. 1108.2.9.1] 2. Please provide the location of the accessible portion of the point of sale/service counter. [Ref. IBC 2018 Sec. 904.1] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS Sheet E3.0 1. Please provide updated short-circuit calculations for the relocated panels. [Ref. NEC 2017 Art. 110.10] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
02/06/2025 | Fire New Construction Standard | REVIEW COMPLETED | Alterations to the Fire Alarm or Fire Sprinklers Systems will require a separate submittal. | ||
02/04/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |