Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.2
Permit Number - TC-COM-0125-00197
Review Name: COMMERCIAL REVIEW - FULL REVISION v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/07/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/07/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. Plans submitted for review shall be sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018. 2. The current roof drainage calculations appear to show that the storm water runoff from the existing pitched roof does not contribute to the storm water that is to be drained from the new roof section. Show how this is accomplished or revise the calculations to include the additional storm water runoff. Reference: Section 1106.5, IPC 2018. 3. Provide an overflow scupper for each primary scupper. Reference: Section 1108.1, IPC 2018. [Initial comment: Provide secondary (overflow) roof drainage (see sheet A1.4). Reference: Sections 1108.1, 1108.2 and 1108.3, IPC 2018. |
||
| 09/22/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |