Permit Number: TC-COM-0125-00197
Parcel: 12416158A

Address:
1050 S PARK AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0125-00197
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2025 Commercial Mechanical Standard APPROVED
02/25/2025 Water - PDSD Standard APPROVED
02/26/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/25/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide the sealed structural calculations used to design this project with the next submittal. IBC 107.2.1
2. Please provide the special inspection certificate with Part A, and Part B, completed with next submittal. IBC 107.2.1
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf
3. Please provide more information and demonstrate on the drawings, the written operation of the controlled access doors. IBC 107.2.1 List the sequence of operation indicating all the actions that will lock and unlock the doors.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
02/12/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0125-00197 (1050 S PARK AV TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Update the panel schedule for the existing panel LD. Show the new panel ‘D’ in the panel schedule. Currently this panel schedule for panel ‘LD’ shows to (E)Panel ‘C’s. NEC arts;300 and 408.4.
2. Update the panel schedule for the new panel ‘D’ to provide breaker and conductor sizes for all the new loads. Lights and rec-restrooms are missing required information in the panel schedule. NEC arts;300 and 408.4.
3. NOTE: There is a plumbing page, P4.0, mixed in with the electrical pages. Please have this page placed in the correct location with in the complete plan-set.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/25/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Revise detail 208 (Ejector Pump Detail) to provide a check valve between the full-open valve and the ejector pump. Reference: Section 712.2, IPC 2018.
2. Provide a detail showing how the ejector pump discharge connects to the horizontal branch drain above the ceiling per Section 712.3.5, IPC 2018.
3. Show the required revisions to the existing natural gas piping to serve the relocated unit heater (see Unit Heater Detail 104, M2.0).
02/12/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0125-00197 (1050 S PARK AV TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
1. Additions or modifications to outdoor lighting less than 25% of total lighting shall require a complete inventory and site plan detailing all existing and any proposed new lighting, OLC 102.4. One additional outdoor is being added, lighting fixture “B”.
2. New or modified lighting shall meet the requirements of this code regarding shielding, and lamp type, OLC 102.4
3. Or Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2 or show the exterior light as full-cutoff and under a canopy or overhang, OLC 401.2.1 item 3.
4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
5. Submit catalogue or specification sheets of all proposed outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/26/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0125-00197
10552 S Park AV

Site engineering comments are as follows:
1. Development Package TD-DEV-0125-00197 must be approved by all reviewers prior to approval of this building permit. UDC Article 3.3.3
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
02/25/2025 Site Zoning Standard REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0125-00197 - TD-DEV-0125-00008
1050 S PARK AV . – I-1
Shelter Care (1st Review)

TRANSMITTAL DATE: February 25, 2025

DUE DATE: February 25, 2025

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the I-1 (UDC 4.7.29). Shelter Care is an allowed use in the zone (UDC Table 4.8-5) subject to Use Specific Standards 4.9.7.J.1, 3.d, .4, .5, .6, and 4.9.13.Q

1. COMMENT: As Development Package (DP) TD-DEV-0125-00008 has not completed its first review Zoning will not review the building plans at this time. Once the DP has completed its first review Zoning will review for compliance.

2. It does not appear that the proposed addition meets the requirements of Use Specific Standard 4.9.7.J.6. Per discussions with the Elisa Hamblin, Zoning Administrator, a Board of Adjustment for Variance will need to be submitted and approved prior to approval of this building plan and the required development package (DP). The Board of Adjustment shall be addressed during DP review.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/06/2025 Fire New Construction Standard REVIEW COMPLETED Fire Alarm or Fire Sprinklers alterations requires a separate submittal. City Of Tucson Adopted Fire Code is the 2024 IFC.
02/03/2025 PDSD Application Completeness Express REVIEW COMPLETED