Permit Number: TC-COM-0125-00173
Parcel: 112064260

Address:
2475 E WATER ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0125-00173
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2025 Commercial Building Standard APPROVED
04/02/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/02/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0125-00173 (2475 E WATER ST TUCSON, AZ 85719)

1. Show electrical branch circuit, wiring methods and location of the new drinking fountain, NEC arts;300 and 408.4.
04/02/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Specify the minimum exhaust flow rate for each restroom. [Initial comment: Specify the minimum exhaust flow rate for each restroom. Reference: Section 107.2.1, IBC 2018 and Section 403.3.1.1, IMC 2018.]
04/02/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Provide specifications and listing information for the proposed drinking fountain. Reference: Section 303.4, IPC 2018. [Initial comment: The plumbing fixture count calls for providing one drinking fountain but no drinking fountain is shown. Note that Section 410.3, IPC 2018 calls for no less than two drinking fountains for accessibility.]
03/11/2025 PDSD Application Completeness Express REVIEW COMPLETED