Permit Number: TC-COM-0125-00173
Parcel: 112064260

Address:
2475 E WATER ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0125-00173
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2025 Commercial Electrical Standard APPROVED
07/23/2025 Outdoor Lighting Standard APPROVED
07/14/2025 Site Engineering Standard NOT REQUIRED
07/31/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/31/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please amend plans to provide sections through the vestibule to show or provide references to detailed drawings showing the following. IBC 107.2.1
A. Door threshold heights and transitions
B. Floor/landing slope between door sets and show the landing outside the exterior doors
C. Provide header design and drawings over the openings
D. Indicate the attachment at the top of the new exterior walls to the canopy above.
2. Sheet A2.1: Please amend plan detail 3/A2.1 to indicate the 2” minimum weep screed clearance above a paved surface and 4” above grade. IBC 2512.1.1
3. Sheet A2.1: Please note or otherwise indicate the glazing shown in the vestibule doors and windows details 4&5/A2.1 is tempered safety glazing. IBC 2406.4.2
4. Sheet M1.1: Please amend the plan to show the method of return air for the vestibule. IMC Chapter 4.

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/31/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 4. Sheet M1.1: Please amend the plan to show the method of return air for the vestibule. IMC Chapter 4.
07/30/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0125-00173
2475 E WATER ST. - C-2
Site Fencing (1st Review)

TRANSMITTAL DATE: ‎July 30, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21).

1. The proposed vestibule constitutes an expansion of gross floor area and per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/25/2025 Fire New Construction Standard REVIEW COMPLETED
07/11/2025 PDSD Application Completeness Express REVIEW COMPLETED