Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0125-00160
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/24/2025 | Commercial Building Standard | REQUIRES RESUBMIT | 1. Please amend the structural calculations to add the Designer’s seal, signature, and date signed on all necessary sheets. IBC 107.1 2. Please provide the special inspection certificate with Part A, and Part B, completed with next submittal. IBC 107.2.1 https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf 3. Please amend the Floorplan bathroom drawing to show the required 5-foot water closet clearance, minimum in width, measured perpendicularly from the sidewall. 2009 ICC A117.1 604.3.2 |
||
| 02/10/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0125-00160 (8284 S CAMINO DE CAFE TUCSON, AZ 85747) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide GFCI protection for all receptacles in the storage/garage area per NEC 210.8(B)(8). Reference section 100 for definitions. 2. Provide the electrical and mechanical requirements of the instant water heater and bathroom fan. 3. Provide complete compliance with the 2018 IECC for the interior and exterior lighting where applicable. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 02/19/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Specify the air flow rate for the bathroom exhaust fan. Reference: Section 403.3.1.1, IMC 2018. | ||
| 02/19/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Provide a site plan showing the installation of the water service to the building and the installation of the building sewer. Reference: Sections 107.2.1 and 107.2.6, IBC 2018. 2. Verify the size of the proposed building sewer. It is called out as 4” on the development plan (TD-DEV-0724-00196) but 3” on sheet P1.0. Reference: Section 107.2.1, IBC 2018. 3. Revise the testing procedure for gravity waste, soil, and vent systems to require a minimum head of ten feet of water (see Plumbing Notes, sheet P1.0). Reference: Section 312.6, IPC 2018. 4. Provide third-party listing and material standards for all plumbing fixtures. Reference: Sections 303.4 and 402, IPC 2018. 5. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 6. Provide specifications for the “utility sink with bottle filler per owner” noted on sheet P1.0. The use of a point-of-use water dispenser in lieu of a drinking fountain requires the installation of a listed and labeled water dispenser along with a permanently mounted disposable cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34” and 48” above the finished floor. See: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/2008-21_e_drinkingfountainpolicy.pdf 7. Provide the specifications and listing information for the proposed instant water heater. Reference: Sections 303.2 and 501.5, IPC 2018 and Section 107.2.1, IBC 2018 8. Clarify why hot water is not being supplied to the service sink. Reference: Section 607.1, IPC 2018. 9. Provide calculations to show that the specified rain gutter at a slope of 1/16” per 12” has the capacity to carry the rain load without overflow of the gutter (Table 1106.6 shows a minimum slope of 1/8” per 12”). Reference: Section 1106.6, IPC 2018. |
||
| 02/10/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-0125-00160 (8284 S CAMINO DE CAFE TUCSON, AZ 85747) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: 1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2 or show the exterior light as full-cutoff and under a canopy or overhang, OLC 401.2.1 item 3. 2. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 3. Submit catalogue or specification sheets of all proposed outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 02/24/2025 | Site Engineering Standard | REQUIRES RESUBMIT | TC-COM-0125-00160 8284 S CAMINO DE CAFÉ Site engineering comments are as follows: 1. Please revise the parking layout to match that shown on the associated development package, TD-DEV-0724-00196, or submit a revision to the DP. Ryan Insalaco – ryan.insalaco@tucsonaz.gov |
||
| 02/24/2025 | Site Zoning Standard | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0125-00160 - TD-DEV-0724-00196 8284 S CAMINO DE CAFE - I-1 Craftwork (1st Review) TRANSMITTAL DATE: February 24, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the I-1 zone (UDC 4.7.29). Craftwork is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.5.C.2, .6, .7, & .8 and 4.9.13.Q. 1. The accessible parking layout shown on the site plan, sheet SP1 does not match the layout shown on the DP. 2. Provide building height dimensions on sheet A2.1. Building height is the vertical distance measured from the design grade elevation to the highest point of a flat roof; to the deck line of a mansard roof; or to the middle (between the eave and ridge ) of the highest gable of a pitched or hipped roof, except as follows. See UDC Article 6.4.4.A & Figure 6.4.4-A. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 02/19/2025 | Water - PDSD Standard | REQUIRES RESUBMIT | Verify the size of the proposed water meter. It is called out as 1” on the development plan (TD-DEV-0724-00196) but 5/8” on sheet P1.0. Reference: Section 107.2.1, IBC 2018. | ||
| 02/05/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 01/31/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |