Permit Number: TC-COM-0125-00159
Parcel: 140270840

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0125-00159
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2025 Site Zoning APPROVED
02/26/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/25/2025 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide construction drawings including details for the assembly of the Cold Panel Box. Additionally, show floor, wall, roof and door details on the plans IBC 107.2.1
2. Please upload the manufacturer’s installation manual with the next submittal. IBC 107.2.1
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
02/12/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0125-00159 (2681 E WIEDING RD TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Show the location of the panels on the Electrical Plan with clear working space compliance, 2017 NEC 110.26(A).
2. Verify Circuit LA-40/42 conductor size. Overcurrent protection shall not exceed
20 amperes for #12AWG CU conductors, NEC 240.4(D).


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/26/2025 Commercial Mechanical REQUIRES RESUBMIT 1. Provide the operating conditions (e.g. temperature range) for the cold box. Reference: Section 107.2.1, IBC 2018.
2. Provide the specifications for the refrigeration system used to maintain the conditions within the cold box (e.g. refrigerant type, quantity of refrigerant, etc.). Reference: Section 11104, 1105, and 1106, IMC 2018.
3. Show that the cold box complies with the construction and energy-use requirements of Sections C403.10.2 and C403.10.2.1, IECC 2018.
02/11/2025 Fire New Construction REVIEW COMPLETED
02/11/2025 PDSD Application Completeness Express REVIEW COMPLETED