Permit Number: TC-COM-0125-00139
Parcel: 141186530

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0125-00139
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2025 Commercial Electrical Standard APPROVED
02/05/2025 Outdoor Lighting Standard APPROVED
02/13/2025 Water - PDSD Standard APPROVED
02/20/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/19/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved.
1. Please amend plans to provide a list of deferred submittals on the cover or code data sheet with a note to not install until approved. IBC 107.3.4.1
2. Please provide the GEOTECHNICAL REPORT 24-077 BY PATTISON ENGINEERING, LLC DATED OCTOBER 31, 2024, with your next submittal. IBC 107.2.1
3. Please provide the special inspection certificate with Part A, and Part B, completed with next submittal. IBC 107.2.1
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
02/13/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted (i.e. all of the air supplied to the restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.
02/13/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Provide a site plan showing the installation of the water service to the building and for the installation of the building sewer from the building to the connection to the public sewer. Reference: Sections 107.2.1 and 107.2.6, IBC 2018.
2. Termination of the excess pressure relief from the water heater, P8, over an elevated service sink, P4, is not an approved location. Reference: Section 504.6 (6), IPC 2018.
02/20/2025 Site Engineering Standard REQUIRES RESUBMIT 1. Until the Development Package is approved engineering can't approve the building permit.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
02/20/2025 Site Zoning Standard REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: TC-COM-0125-00139 - TD-DEV-0125-00006
10096 E OLD VAIL RD. – PAD-36
Membership Organization – Site Wall (2nd Review)

TRANSMITTAL: February 20, 2025

This site is located in PAD-36 (UDC 4.7.24). Automotive: Minor Service and Repair is an allowed use in the PAD.

1. As TD-DEV-0125-00006 has not completed its first review Zoning is not able to review the building plans for compliance with the DP.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/06/2025 Fire New Construction Standard REVIEW COMPLETED 1. Install fire extinguishers as required by the 2024 IIFC Section 906.
2. Install an NFPA 704 Diamond at the oil -chemical storage room-door.
01/29/2025 PDSD Application Completeness Express REVIEW COMPLETED