Permit Number: TC-COM-0125-00107
Parcel: 117200280

Address:
151 S GRANADA AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0125-00107
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2025 Water - PDSD Standard APPROVED
02/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/31/2025 Commercial Building Standard REQUIRES RESUBMIT Sheet G1.0; For questions regarding Plan Review comments please contact: Dino M. Accardo, MCP, CBO, E: daccardo@willdan.com. Fire Plan Review is NOT within the scope of this review. All applicable comments will be followed with the initials, DMA.

1. Sheet G1.0, 2018 IBC 107.1 and 107.2; Provide foundation structural details and calculations. A foundation is a critical structural portion of a building structure and is subject to review prior to occupancy. Include geotechnical reports. DMA
2. Sheet G2.0, 2018 IBC 302.1 Occupancy classification. Occupancy classification is the formal designation of the primary purpose of the building, structure or portion thereof. Structures shall be classified into one or more of the occupancy groups listed in this section based on the nature of the hazards and risks to building occupants generally associated with the intended purpose of the building or structure. A occupancy listed is incomplete. NOTE: Once correct and applicable occupancy classification is provided, this will be subject to review including but not limited to code section and impacts. Provide supporting narrative that describes use of proposed building. DMA
3.Sheet G2.0, 2018 IBC 1010.1.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons. DMA
4. Sheet G2.0; Specify in Code Analysis if building is sprinklered, and list the existing building occupancy classification prior to the proposed remodel. DMA
5. Sheet S1.0, 2018 IBC Ch17, Submit a completed Tucson Special Inspection Certificate. DMA
6. Sheet S1.0, 2018 IBC Ch 16; Submit a complete set of structural calculations. DMA
7. Sheet A8.0, 2018 IBC Ch 10; Provide hardware schedule and list on door schedule. DMA
8. Sheet A9.1, 2018 IBC Ch 10 and 11; Provide dimensions of ramp and slope for review include detail with top view of ramp. DMA
01/31/2025 Commercial Electrical Standard REQUIRES RESUBMIT
01/31/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Sheet M4.0, 2018 IMC 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm (0.9 m3/s), in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. DMA
2. Sheet M4.0, 2018 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Provide Outdoor Air Calc. NOTE: Also see comment regarding submittal of a compliant applicable occupancy classification; this must be coordinated with the design once occupancy is established. DMA
01/31/2025 Commercial Plumbing Standard REQUIRES RESUBMIT
01/31/2025 Outdoor Lighting Standard REQUIRES RESUBMIT
02/10/2025 Site Engineering Standard REQUIRES RESUBMIT 1. The associated development package TD-DEV-0624-00174 must be approved before this building permit can be approved.

Mike Ortiz
michael.ortiz@tucsonaz.gov
02/07/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0125-00107 - TD-DEV-0624-00174
151 S GRANADA AV. - PAD-5
Community Center Facilities (1st Review)

TRANSMITTAL DATE: ‎February 7, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-3 zone (UDC 4.7.22). Commercial Storage use is a permitted use in the zone (UDC Table 4.8-4).

1. Zoning has reviewed the building permit for compliance with development package (DP) TD-DEV-0624-00174 and although it appears that the building plan is in compliance until the DP is approved by all review agencies Zoning cannot approve this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
01/27/2025 Fire New Construction Standard REVIEW COMPLETED
01/17/2025 PDSD Application Completeness Express REVIEW COMPLETED