Permit Number: TC-COM-0125-00107
Parcel: 117200280

Address:
151 S GRANADA AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0125-00107
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2026 Commercial Building Standard APPROVED
01/30/2026 Commercial Electrical Standard APPROVED
01/30/2026 Commercial Mechanical Standard APPROVED
01/30/2026 Commercial Plumbing Standard APPROVED
01/28/2026 Design Review Standard APPROVED Minor historic preservation review was approved today. If you have any questions, please let me know: maria.gayosso@tucsonaz.gov.
01/28/2026 Historic APPROVED Minor review conducted and recommended approval for the change in fenestration openings on East elevation.
01/29/2026 Site Zoning Standard APPROVED Approved with TD-DEV-0624-00174 and SD-1024-0010
01/27/2026 Water - PDSD Standard APPROVED
01/30/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/26/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0125-00107 (151 S GRANADA AV TUCSON, AZ 85701)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf


1. Provide compliance with the outdoor lighting code maximum unshielded lumens per Table 401.1. See also OLC 102.4. Possible solution would be to remove the existing string light fixture/s.
01/29/2026 Site Engineering Standard REQUIRES RESUBMIT Site Engineering Review

TC-COM-0125-00107
151 S GRANADA AV

Summary: Remodel Existing Sosa-Carillo House Associated with SD-1024-00104

Site Engineering comments are as follows:

1. The landscape planter design on this commercial building permit does not match that depicted on the revised associated development package, TD-DEV-0624-00174.
2. Please address the changes in the keynotes/call-outs for which pavers are to remain and which are to be replaced.
3. Please re-submit this permit once either building permit is corrected, or the development package is revised to reflect the incongruences.

To re-submit, visit the Tucson Development Center Online at:
https://tdc-online.tucsonaz.gov/#/home

The instructions for resubmittal can be found at: Revisions and Resubmittals

Engineering Associate: Ryan Insalaco
ryan.insalaco@tucsonaz.gov
01/27/2026 Fire New Construction Standard REVIEW COMPLETED
01/23/2026 PDSD Application Completeness Express REVIEW COMPLETED Revision missing revision letter.