Permit Number: TC-COM-0124-00199
Parcel: 129091410

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0124-00199
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2024 External Reviewers - SAFEBuilt APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 5/31/2024 2:11:06 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/30/2024 1:52:51 PM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 2/12/2024 7:22:00 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 5/29/2024 3:33:19 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 5/29/2024 3:33:19 PM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 6/1/2024 4:55:18 PM
Second Plumbing Review: OK

Resolved-1). Need to address Roof drainage Bldg comment 1, -2018 IPC 1101.7, 1106.1, 1106.2, 1106.6, 1106.3

Resolved-2). Label unit heater exhaust on plan page M1.0 -2018 IFGC 503.1

Resolved-3). Add unit heater exhaust to M3.0 Unit heater detail. - 2018 IFGC 503.1

Resolved-4). add note to top of plan page P1.0 to terminate condensate drain 12" from Bldg. -2018 IBC

Resolved-5). Plan set needs show required existing high/low drinking fountain location & distances from furthest point of new addition to the High/Low drinking fountain. . -2018 IPC 403.1, 403.5

Resolved-6. Plan set need to show required existing service sink location. -2018 IPC 403.1

Resolved-7). Plan set needs to show distances from furthest point of new addition. to existing restrooms. -2018 IPC 403.3
05/13/2024 Site Zoning APPROVED
06/04/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/10/2024 Site Engineering REQUIRES RESUBMIT 1. The footprint of the proposed building (square feet) is not consistent across sheets within the current site plan and does not match the approved development package. Please ensure the footprint is consistent across all sheets and matches the approved development package.

Mike Ortiz
michael.ortiz@tucsonaz.gov
04/12/2024 PDSD Application Completeness REVIEW COMPLETED