Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-0124-00151
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/08/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/06/2024 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-0124-00151 (4420 S 6TH AV TUCSON, AZ 85714) 3rd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). >>> These comments were not addressed: 1. Provide structural design, details, construction drawings and calculations for the new carport prepared by Arizona licensed registrant. IBC 107.2.1 2. Provide a Grounding Electrode System at the detached structure per NEC 690.47. 3. Show grounding details for the mounting equipment and metal support frame, NEC690.43. Grounding details must include the new grounding of the new detached carport structure. |
||
| 08/08/2024 | Commercial Structural | REQUIRES RESUBMIT | Applicant resubmitting updated drawings. | ||
| 08/08/2024 | Site Engineering | REQUIRES RESUBMIT | Applicant resubmitting updated drawings. | ||
| 08/08/2024 | Site Zoning | REQUIRES RESUBMIT | Applicant resubmitting updated drawings. | ||
| 07/22/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |