Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0124-00101
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2024 Commercial Mechanical APPROVED
01/29/2024 Commercial Plumbing APPROVED
02/02/2024 Commercial Structural APPROVED
01/18/2024 Site Zoning APPROVED
01/24/2024 Site Engineering NOT REQUIRED
02/02/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/31/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The branch circuit designation shows panel ‘A’. The panel schedules show panels ‘1’ and ‘2’? Please clarify. NEC 408.4

Identify the units on the power plan.

Provide arc fault protection for the 120-volt washer receptacle, NEC 210.12A

Ref; 2018 IBC sections 107.2.1, 2017 NEC
01/19/2024 Fire New Construction REVIEW COMPLETED
01/18/2024 PDSD Application Completeness REVIEW COMPLETED It appears the locations added and permit documents uploaded lists multiple units. Please note each unit must be separate from one another and requires it's own permit. This permit is for the identified 207 N MAGUIRE AV BLDG E UNIT 142 only, please start new permits for all other buildings and its associated unit. The other address listed 207 N MAGUIRE AV BLDG E UNIT 242 will be removed off of this permit.