Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0124-00081
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/23/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/23/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide the developed pipe length, pipe sizes and pipe material from the gas meter to the pool heaters (i.e. not just to the building entry). Include the number and size of any fittings within the building. 2. Provide the minimum gas pressure for the pool heaters per the manufacturer. Per Table 402.4(21), IFGC 2018, 2” SDR 11 polyethylene pipe can deliver only 1110 CFH for 80 feet with a 0.5’ WC drop. |
||
01/12/2024 | PDSD Application Completeness | REVIEW COMPLETED |