Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0124-00081
Parcel: 10503002B

Address:
60 W STONE LP

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0124-00081
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/23/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Provide the developed pipe length, pipe sizes and pipe material from the gas meter to the pool heaters (i.e. not just to the building entry). Include the number and size of any fittings within the building.
2. Provide the minimum gas pressure for the pool heaters per the manufacturer. Per Table 402.4(21), IFGC 2018, 2” SDR 11 polyethylene pipe can deliver only 1110 CFH for 80 feet with a 0.5’ WC drop.
01/12/2024 PDSD Application Completeness REVIEW COMPLETED