Permit Number: TC-COM-0124-00041
Parcel: 12509012A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0124-00041
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/26/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 6/26/2024 8:36:45 AM
1. Resolved - Sheets P1.0, P2.0: Include the location, specifications, and calculations for the grease interceptor on the floor plan piping layout and the isometric diagrams. (2018 IPC section 1003, Amended sections 1003.3)

2. Unresolved - Sheets P1.0, P2.0: The hand wash sinks are required to be connected to the grease interceptor or post a sign stating “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” (2018 IPC amended section 1003.3) The waste diagram still shows a hand wash sink (P4) not connected to the grease waste system.

3. Resolved - Sheet P1.0: Include the faucet details meeting the requirements of the 2018 IPC amended sections 412.11 and 419.6.

4. Unresolved - Sheet P2.0: Include the water supply piping isometric. (2018 IBC section 107) Not included.
06/25/2024 PDSD Application Completeness Express REVIEW COMPLETED