Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0124-00041
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/26/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/26/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Plumbing(P) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 6/26/2024 8:36:45 AM 1. Resolved - Sheets P1.0, P2.0: Include the location, specifications, and calculations for the grease interceptor on the floor plan piping layout and the isometric diagrams. (2018 IPC section 1003, Amended sections 1003.3) 2. Unresolved - Sheets P1.0, P2.0: The hand wash sinks are required to be connected to the grease interceptor or post a sign stating “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” (2018 IPC amended section 1003.3) The waste diagram still shows a hand wash sink (P4) not connected to the grease waste system. 3. Resolved - Sheet P1.0: Include the faucet details meeting the requirements of the 2018 IPC amended sections 412.11 and 419.6. 4. Unresolved - Sheet P2.0: Include the water supply piping isometric. (2018 IBC section 107) Not included. |
||
06/25/2024 | PDSD Application Completeness | REVIEW COMPLETED |