Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0124-00028
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/19/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/17/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. Ref; Plan Sheet E1.0, Outdoor lighting Calculations. 1. It appears that the total lumens for the Parcel (14.46 acres), is not included in the total lumen calculations as required per OLC section 104.2.1(2)(3). Per telephone conversation on 1-17-2024 with the EE of record, the information required may require a complete assessment of the entire site and would possibly be a burden imposed on the owner of the site. Also, per the EE of record, the 4 new exterior luminaires would be for maintenance purposes only, and for the safety of personal required to perform maintenance to the equipment after sundown. Due to luminaires being equipped with Full Cut-Off Shielding, Lamp color temperature output not exceeding 3500K, and being installed inside a 9’ Masonry walled equipment yard. The City PDSD plan reviewer will allow the option of, in lieu of providing lumen calculations for the entire parcel, the EE of record will provide for 2 hour mechanical lighting timers to operate the 4 new luminaires to ensure the lighting is not accidently left on after the maintenance work is completed for the night. Ref; 2018 IBC 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code (OLC). |
||
01/18/2024 | Commercial Mechanical | REQUIRES RESUBMIT | The proposed air-cooled chillers do not appear to meet the minimum performance requirements of Section C403.3.2, IECC 2018, Table C403.3.2(7) for full load EER for either Path A or Path B. | ||
01/19/2024 | Commercial Structural | REQUIRES RESUBMIT | Structural Calculation is missing the Engineer's seal/singnature/date. | ||
01/05/2024 | PDSD Application Completeness | REVIEW COMPLETED |