Permit Number: TC-COM-0123-00509
Parcel: 115185450

Address:
1620 N HALRON CT

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0123-00509
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2023 Site Engineering APPROVED
03/03/2023 Site Zoning APPROVED
03/08/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/27/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0123-00509

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
1. Foundations are not part of this approval.
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Denied
1. Sheet G1.01: No occupant load calculations have been provided. Provided detailed occupant load calculations in accordance with Section 1004.
2. Sheet G1.01: Provide the location of all proposed furniture and storage system layouts on the egress plans.
3. Sheet G1.01: Provide the room location names to ensure proper occupant load calculations.
4. Sheet A1.04 The RCP does not show the location of egress illumination and exit signage. Provide the location of egress illumination and exit signage in accordance with Section 1008 and 1013.


MECHANICAL REVIEW COMMENTS:
Denied
1. Provide information as to what products are being stored in this warehouse (IMC2018,106.3.1)
2. Provide information as to what type for forklifts are being used whether fuel powered or electric powered (IMC2018,106.3.1)


ELECTRICAL REVIEW COMMENTS
Denied
e1.0 POWER / SYSTEMS PLAN: Keynote #2 calls out for a 2 pole disconnect, but actual circuits are 3 phase ie circuit A2,4,6 and others. Correct Keynote or circuits as required.
e2.0 LIGHTING PLAN:
Math is wrong for IECC actual Connected Lighting Power Column. Should correct.
Keynote #2 seems to actually be Keynote #1. Correct or clarify as required.
e3.0 ELECTRICAL SCHEDULES: Sheet has two panel As, need to submit panel schedule B.
e4.0 ELECTRICAL SPEC & LEGEND: No electrical issues


PLUMBING REVIEW COMMENTS:
Denied
e1.0 POWER / SYSTEMS PLAN: Keynote #2 calls out for a 2 pole disconnect, but actual circuits are 3 phase ie circuit A2,4,6 and others. Correct Keynote or circuits as required.
e2.0 LIGHTING PLAN:
Math is wrong for IECC actual Connected Lighting Power Column. Should correct.
Keynote #2 seems to actually be Keynote #1. Correct or clarify as required.
e3.0 ELECTRICAL SCHEDULES: Sheet has two panel As, need to submit panel schedule B.
e4.0 ELECTRICAL SPEC & LEGEND: No electrical issues


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/08/2023 Fire New Construction REQUIRES RESUBMIT SHEETS c0.01 (SEE G1.01 FOR SMOKE DETECTION) & SMOKE DETECTOR NOTE
SHEET G1.01 FIRE NOTES: SMOKE ALARMS, PLEASE REMOVE THESE NOTES AS THEY ARE NOT REQUIRED FIRE SYSTEMS FOR THE BUILDING.

Questions:

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
02/08/2023 PDSD Application Completeness Express REVIEW COMPLETED