Permit Number: TC-COM-0123-00423
Parcel: 123100280

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0123-00423
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2023 Site Zoning APPROVED
01/26/2023 Site Engineering NOT REQUIRED
01/31/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
01/27/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0123-00423

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.

BUILDING REVIEW COMMENTS:
Conditionally Approved
Building review is hereby approved with the following stipulations:
1. Complete City of Tucson Building Department Special Inspection Certificate as follows:
◦ Part A to indicate name and license number of construction contractor;
◦ Part A must complete owner or legal agent signature;
◦ Part B - Engineer of record (EOR), must meet all requirements as stated in the City of Tucson 2018 IBC, Section 1703 - 1703.6.2.
◦ Part C to be completed prior to issuance of occupancy certificate.
2. Verification & Inspection of Concrete Construction on page S001 shall no longer refer to Section 1912.1 under concrete-filled pipe columns (2015 IBC), but to Section 1901.3 (2018 IBC, enforced by the City of Tucson 1/2/2019).
Anchoring to Concrete shall be in accordance with manufacturer requirements and ACI 318 as amended in Section 1905, and applies to cast-in (headed bolts, headed studs and hooked J- or L-bolts), post-installed expansion (torquecontrolled and displacement-controlled), undercut and adhesive anchors.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Denied
E101 FIRST FLOOR ELECTRICAL DEMO AND POWER PLAN: Could not locate Keynote 8.
E801 ONE-LINE DIAGRAM & PANEL SCHEDULES:
New Dist Panel L#C-151 has 400 amp bus with 600 amp CB. Probably not available. 600 Amp CB is oversized for existing feeder (or show feeder size for reviewer). Resize as required.
Should estimate current load for existing circuits. Should not leave as 0 unless there is no load on these branches.
Calculated loading for L3C-152 is in error. Use 277V to neutral, not 480V. Also missing loads of CT Scan Rm 1126 and Radiation Rm 1125 (may be intermittent and not needed, EOR decision).


PLUMBING REVIEW COMMENTS:
Conditionally Approved
First Plumbing Review: Ok Subject to Field Inspections


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
01/11/2023 Fire New Construction REVIEW COMPLETED
01/10/2023 PDSD Application Completeness REVIEW COMPLETED