Permit Number: T22CM08170
Parcel: 141177510

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - T22CM08170
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
04/15/2024 External Reviewers - Stantec REQUIRES RESUBMIT April 15, 2024
2nd Review

a23 studios
Attn: Burak Bekat
711 E. 9th Street
Tucson, Arizona 85719

Re: MISTER CARWASH
NEW BUILDING – DEFERRED SUBMITTAL

City of Tucson Permit Number: T22C08170
Stantec Project Number: 185215009
Stantec File Number: TUC-24-031

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. To facilitate a shorter back-check time, we request that you please, only provide plans and calculation pages that have been revised, clouding any changes, along with a written response to each of the noted items indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 5,381 278 No No
Separate Permits: Signage.
Deferred Submittals: POS canopies, vacuum station canopies, premanufactured trusses, and storefront.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, field welding, masonry, and outdoor lighting.

GENERAL COMMENTS

1. Addressed.

2. New Comment: Please remove the additional truss layout from the submittal that does not include the review comments.

ARCHITECTURAL COMMENTS

There are no comments.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

1. New Comment: This comment is due to the addition of the truss calculations which were not part of the first submittal. Please revise the mechanical and plumbing plans to coordinate with the location of the RTUs on the architectural and structural plans. The truss layout indicates that the units are to be placed per structural and architectural.

PLUMBING COMMENTS

1. New Comment: This comment is due to the addition of the truss calculations which were not part of the first submittal. Please revise the mechanical and plumbing plans to coordinate with the location of the RTUs on the architectural and structural plans. The truss layout indicates that the units are to be placed per structural and architectural.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/08/2024 PDSD Application Completeness REVIEW COMPLETED