Permit Number: T22CM08148
Parcel: 12212015C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM08148
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2022 Fire New Construction APPROVED
10/31/2022 Site Engineering APPROVED
12/12/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/05/2022 Commercial Plumbing REQUIRES RESUBMIT Provide the civil site utility plans showing the construction of the water service to the new building. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand to be served by the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018.
11/04/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM08148

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. General: Provide the site geotechnical report. (2018 IBC Sec. 1803.1)
2. Sheet S0.000 (General Notes) / Design Criteria / Live Loads: Please indicate the live loads for the storage mezzanine. (2018 IBC Sec. 1607)
3. Sheet S3.001 (Sections and Details) / 7/S3.001 (Slab Depression at Oil Tank): Clarify if the design includes seals at the cold joints to minimize liquid escaping from this secondary containment pit.


BUILDING REVIEW COMMENTS:
Denied
1. (Provided for information / Response Not Required): A review to determine compliance with the International Fire Code was not performed; however, the following concerns were observed: the lack of vents on the waste oil storage tanks, the design of the secondary containment for the oil storage tanks, required signage around the tanks, etc.
2. General: Clarify the oil change process at this proposed location. Detail 08/A5.101 shows a pit only 2’-6” deep, while most oil change locations use a basement space to allow standing staff to access the underside of the vehicles. Will this location rely on vehicle lifts, which are not reflected on the electrical sheets? Please clarify the method of operation.
3. General: Indicate the method of compliance with the 2018 International Energy Conservation Code (2018 IECC) for the building thermal envelope. The information must include the R-values for the walls and ceilings, with the U-factors and SHGC for glazing panels. (2018 IECC Sec. C401.2, C402.1 & C402.4)
4. Sheet G1.001 / Basic Building Data / Building Height: This is unsprinklered building and the information indicates that two stories would be “allowed per 503”. Please revise to indicate that one story is provided and allowed per 2018 IBC Table 504.4 for a Group S-1 using Type V-B construction.
5. Sheet G1.001 / Exit Requirements / Number and Arrangement of Exits: This table indicates the maximum travel distance is 100’-0”, while 2018 IBC Table 1017.2 allows up to 200’-0” for an unsprinklered Group S-1 occupancy. Please revise.
6. Sheet G1.001 / Exit Requirements / Number and Arrangement of Exits: This table and the Life Safety Plan – Level 01 appear to show the path of egress travel from the Manager’s Office to the exit discharge through the Equipment Room / Waste Oil storage space. Please revise to indicate that the travel distance is measured from the most remote point inside the building, per 2018 IBC Sec. 1017.3. This measure should reflect a point near one of the far corners in the service bay area, while the occupant navigates around the open pits.
7. Sheet G1.001 / Attic Level Plan: Please align this plan view to match the orientation of the Life Safety Plan – Level 01. It is assumed that the Mezzanine is over the Manager’s Office, Equipment Room / Waste Oil, and Restroom.
8. Sheet G1.001 / Attic Level Plan: Per 2018 IBC Sec. 1011.14 alternate tread devises are limited to mezzanines with an area of 250-ft2 or less within Group F, H, and S occupancies. Please revise the design of the mezzanine access or reduce the area of the mezzanine.
9. Sheet G1.001 / Life Safety Plan – Level 01 / Function of Space Legend: Clarify that the yellow color represents the primary occupancy and not an accessory use.
10. Sheet G1.001 / Life Safety Plan – Level 01: Show the path of egress travel from the most remote location, per 2018 IBC Sec. 1017.3. This measure should reflect a point near one of the far corners in the service bay area, while the occupant navigates around the open pits.
11. Sheet A2.101 (Building Elevations): The use of EIFS requires special inspections per 2018 IBC Sec. 1705.16, unless installed over a water-resistant barrier. Please provide the installation details from the EIFS manufacturer to achieve compliance with 2018 IBC Sec. 1705.16 Exception #1 or indicate the need for special inspections.


MECHANICAL REVIEW COMMENTS:
Denied
1. General: Indicate the method of compliance with the 2018 International Energy Conservation Code (2018 IECC) for the mechanical systems. (2018 IECC Sec. C401.2)
2. Sheet M1.01 (Mechanical Notes, Details, Schedules, and Floor Plans) / Fan Schedule: This schedule indicates two (02) EF-1 exhaust fans. Please clarify which fan will be used within the restroom. (2018 IMC Table 403.3.1.1)
3. Sheet M1.01 (Mechanical Notes, Details, Schedules, and Floor Plans) / Electric Unit Heater Schedule / IRH: Revise the notes for the radiant heater to comply with the prescriptive requirements of 2018 IECC Sec. C403.12.1. This unit shall be controlled by either a timer or occupancy sensing device to de-energize the unit when occupants are not present.


ELECTRICAL REVIEW COMMENTS
Denied1. Sheet E0.01 (Electrical Specifications and Symbols) / COMcheck: The COMcheck is calculated using the 2007 edition of ASHRAE 90.1; however, the 2018 IECC adopts the 2016 edition of ASHRAE 90.1. (2018 IECC Sec. C401.2 & Chapter 6 (ASHRAE 90.1-2016))


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/01/2022 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T22CM08148
4501 E Speedway Bl
Take 5 (2nd Review)

TRANSMITTAL DATE: October 31, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. The gross floor area of the building in the building plan set exceeds the gross floor area depicted and approved on DP22-0102. Revise the building plan set to ensure the gross floor area is equal to or lesser than the 1,174 square feet shown on DP22-0102.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov.