Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM08126
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2022 Commercial Plumbing APPROVED Water Review
11/01/2022 Site Zoning APPROVED
12/01/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/21/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM08126
GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Refer to Structural Calculations submitted. Page 11 of 18 for Existing Lintel 3-2x12 size shows that it is inadequate in Shear and Bending by 4.2% and 9.7% respectively. Verify and reinforce the lintels as needed.


BUILDING REVIEW COMMENTS:
Denied
1. General: If this building was initially designed using Separated Mixed-Uses per 2018 IBC Sec. 508.1, 508.4 & Table 508.4. Please provide the most recently published complete listed fire resistance assemblies to maintain the separations. (2018 IBC Sec. 703.2 & 707)
2. Sheet CS0.01 (Cover Sheet) / Project Info / Scope of Work: Please revise to include a more detailed scope of work narrative identifying the proposed construction that will be covered under this permit application. (2018 IBC Sec. 107.2.1)
3. Sheet CS0.01 (Cover Sheet) / Accessibility: This project is being identified as an Alteration - Level 1 under the 2018 International Existing Building Code (2018 IEBC); however, the proposed construction involves the reconfiguration of a portion of the floor plan. This is an Alteration - Level 2, per 2018 IEBCC Sec. 603.1. Please revise.
4. heet CS0.01 (Cover Sheet) / Deferred Submittals: It is indicated that "no special inspections" are required. Please reconcile this with Sheet S1.1 where the Structural Engineer is indicating Special Inspections for post-installed anchors as required per 2018 IBC Sec. 1705. 3. Please revise.
5. Sheet CS0.01 (Cover Sheet) / Code Info: This project involves a mixed-use (occupancy) building comprised of a Group A-3 and Group B occupancies. Please clarify if the mixed-use is Separated versus Non-Separated uses, per 2018 IBC Sec. 508.1, 508.3 & 508.4.
6. Sheet CS0.01 (Cover Sheet) / Code Info: Please calculate the allowable area for this mixed occupancy per 2018 IBC Sec. 506.2.2.
7. Sheet G1.01 (Egress Plan): Please revise to include a table showing the design occupant load of each space, the area of the space, the occupant load factor used, and total design occupant load for the building. (2018 IBC Sec. 1004.5 & Table 1004.5)
8. Sheet G1.01 (Egress Plan): If this building was initially designed using Separated Mixed-Uses (occupancies), please indicate the fire resistance rated separations per 2018 IBC Table 508.4
9. Sheet A1.04 (Enlarged Floor Plans): Please clarify the wall finish for the restrooms, specifically around the water closet, per 2018 IBC Sec. 1209.2.2
10. A1.06 (Window & Door Schedules): Indicate the U-factor and SHGC for the new glazing and skylights. (2018 IECC Sec. C402.4)


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Denied
No electrical included in design to review. Electrical permit Denied


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). Plan page A1.04 needs to show restroom fixture spacing - side wall or partition to fixture center all restroom fixtures, fixture to fixture center separations for lavs & urinals. IPC 404.2, 405.3.1
2). Urinals require partitions, update all affected pages. -IPC 405.3.5
3). Hose Bibbs & cold water building need shut off valves on plan page P1.01. -IPC 606.1, 606.2


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/29/2022 Fire New Construction REQUIRES RESUBMIT
10/31/2022 Site Engineering REQUIRES RESUBMIT Req. Change (Scott) (Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://tdc-online.tucsonaz.gov/#/home, the application can be found under the sub-permits section of this permit.