Permit Number: T22CM08126
Parcel: 106041390

Address:
3435 N 1ST AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - T22CM08126
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2023 Site Engineering NOT REQUIRED
02/15/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/15/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM08126

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
THE RESPONSE LETTER SAYS THAT REVISED CALCULATIONS WITH UPDATED STRUCTURAL LUMBER VALUES ARE ATTACHED AND THE MEMBER "HDR3" IS ADEQUATE.
NO REVISED CALCULATIONS SUBMITTED, THE CALCS SUBMITTED STILL SHOWS MEMBER FAILING.
SUBMIT REVISED CALCULATIONS.
1. Refer to Structural Calculations submitted. Page 11 of 18 for Existing Lintel 3-2x12 size shows that it is inadequate in Shear and Bending by 4.2% and 9.7% respectively. Verify and reinforce the lintels as needed.


BUILDING REVIEW COMMENTS:
Denied
The resubmittal identified as "CONS-1_Plan Set_v1.pdf" does not appear to address the initial review comments. Please resubmit a complete revised plan set with clouds and revision deltas that reflect the revisions requested within the initial review comments.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Denied
Reviewer did not see electrical in his review set, nor were any electrical sheets called out in the sheet schedule on the Cover sheet.
An electrical design will be required for permit because of the following:
A panel is being demo'd or relocated as per D1.01
Plumbing has electric water heaters and Mechanical has HVAC equipment in their designs.
It is suggested to get an engineer to do the electrical design, however Tucson does allow Architects to sign and seal small electrical projects such as this.


PLUMBING REVIEW COMMENTS:
Denied
Second Plumbing Review:
1). SAME-Plan page A1.04 needs to show restroom fixture spacing - side wall or partition to fixture center all restroom fixtures, fixture to fixture center separations for lavs & urinals. IPC 404.2, 405.3.1 **Plan pages need to show the clearance from lav to lav centers and same with the urinals. Also show the sidewall to fixture center distances- IPC 403.1**
2). SAME-Urinals require partitions, update all affected pages. -IPC 405.3.5**List what page the change has been made on in response narrative, plans did not show any updates**
3). SAME-Hose Bibbs need shut off valves on plan page P1.01. -IPC 606.2 **List what page the change has been made on in response narrative, plans did not show any updates**


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
01/30/2023 Fire New Construction REVIEW COMPLETED