Permit Number: T22CM07932
Parcel: 14036017C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM07932
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2023 Site Engineering APPROVED
10/04/2023 Site Zoning APPROVED
10/04/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
09/21/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 9/14/2023 4:01:11 PM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 9/14/2023 10:00:41 AM



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Denied
Reason:
Date Completed : 9/17/2023 12:45:16 AM
1. Provide manufacturers hood specs or if shop made Provide ventilation requirements for shop made hood (e.g type of filters, type of construction of hood, capacity of hood etc) (IMC2018,106.3.1 & 507.1)
2. Provide section and plan view's of appliances under hood to determine overhang requirements (MMC2018,106.3.1)
3. Provide kitchen equipment list (IMC2018,106.3.1)
4. Provide isometric gas pipe riser plan showing the 1. furthest gas run from the meter to the furthest appliance 2. the total gas load in cfh 3. the gas inlet pressure and 4. the pressure drop and 5. the table in the IFGC used to size the gas pipe sheet
M2.1 (IFGC2018,106.3.1)
5. Show how you are complying with the Commercial energy code (software like Comcheck is acceptable) IMC2018,101.5 &101.5.1)



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 9/18/2023 9:20:23 AM
Electrical Review of QT Canopy
By: Ron Ross PE
Approved with the comments below that can be addressed in final inspection.
E610:
a. Sheet still shows Panel T as NEMA 3R.
d. Did not show, and one circuit conflicts with b



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 9/20/2023 11:33:42 PM
Revised plumbing Plan review=Ok Subject to field inspections
09/26/2023 Fire New Construction REVIEW COMPLETED Separate permits required for
installation of:
*fire alarm
*CO2 gas detection alarm
*alarm monitoring
*hood suppression system
*flammable/combustible liquids
for fuel tank installation.
09/12/2023 PDSD Application Completeness REVIEW COMPLETED