Permit Number: T22CM07830
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T22CM07830
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/09/2022 Commercial Electrical REQUIRES RESUBMIT 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
12/12/2022 Commercial Mechanical REQUIRES RESUBMIT 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. The heating/cooling load calculations show two different roofs: 900 square feet that is uninsulated and 900 square feet that is insulated. Is this the actual situation, with 1800 square feet of total roof area? Reference: Section C403.1.1, IECC 2018.
3. Show how the existing HVAC system offsets part of the total calculated heating/cooling load. Reference: Section 107.2.1, IBC 2018.