Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - T22CM07830
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/12/2022 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/09/2022 | Commercial Electrical | REQUIRES RESUBMIT | 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements | ||
12/12/2022 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. The heating/cooling load calculations show two different roofs: 900 square feet that is uninsulated and 900 square feet that is insulated. Is this the actual situation, with 1800 square feet of total roof area? Reference: Section C403.1.1, IECC 2018. 3. Show how the existing HVAC system offsets part of the total calculated heating/cooling load. Reference: Section 107.2.1, IBC 2018. |