Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.3
Permit Number - T22CM07804
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/25/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/25/2025 | Masonry Inspection (Deferred Submittal) Express | REQUIRES RESUBMIT | Field reports are required for Special Inspections. Please resubmit the SIC along with the relevant field report for each special inspection shown on the SIC. | ||
| 07/25/2025 | Other Inspection Reports (Deferred Submittal) Express | REQUIRES RESUBMIT | HIGH STRENGTH BOLTS - Field reports are required for Special Inspections. Please resubmit the SIC along with the relevant field report for each special inspection shown on the SIC. |
||
| 07/25/2025 | Post-Installed Anchor Inspection (Deferred Submittal) Express | REQUIRES RESUBMIT | Field reports are required for Special Inspections. Please resubmit the SIC along with the relevant field report for each special inspection shown on the SIC. | ||
| 07/25/2025 | Welding Inspection (Deferred Submittal) Express | REQUIRES RESUBMIT | Field reports are required for Special Inspections. Please resubmit the SIC along with the relevant field report for each special inspection shown on the SIC. | ||
| 07/25/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |