Permit Number: T22CM07804
Parcel: 13707041B

Address:
5201 S 12TH AV

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.3

Permit Number - T22CM07804
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/25/2025 Masonry Inspection (Deferred Submittal) Express REQUIRES RESUBMIT Field reports are required for Special Inspections. Please resubmit the SIC along with the relevant field report for each special inspection shown on the SIC.
07/25/2025 Other Inspection Reports (Deferred Submittal) Express REQUIRES RESUBMIT HIGH STRENGTH BOLTS -
Field reports are required for Special Inspections. Please resubmit the SIC along with the relevant field report for each special inspection shown on the SIC.
07/25/2025 Post-Installed Anchor Inspection (Deferred Submittal) Express REQUIRES RESUBMIT Field reports are required for Special Inspections. Please resubmit the SIC along with the relevant field report for each special inspection shown on the SIC.
07/25/2025 Welding Inspection (Deferred Submittal) Express REQUIRES RESUBMIT Field reports are required for Special Inspections. Please resubmit the SIC along with the relevant field report for each special inspection shown on the SIC.
07/25/2025 PDSD Application Completeness Express REVIEW COMPLETED