Permit Number: T22CM07804
Parcel: 13707041B

Address:
5201 S 12TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - T22CM07804
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/01/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM07804

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved


BUILDING REVIEW COMMENTS:
Conditionally Approved
Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel, or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The registered design professional is responsible for following ALL applicable Federal, State, and local Municipal Codes and Ordinances.


MECHANICAL REVIEW COMMENTS:
Denied
3. Provide manufacturers specs for hood 1 and hood 2 (IMC2018,106.3.1) this is the information required on the specs which you have not provided Not Complied
5. Provide refrigeration schedule including specs for walk in coolers and freezers and condensing unit information including amount and type of refrigeration (IMC2015,106.3.1) The condensing units for all walk in coolers need to be in the mechanical schedule with all pertinent information Not Complied


ELECTRICAL REVIEW COMMENTS:
Conditionally Approved
E4.0 ELECTRICAL PANEL SCHEDULES: Discrepancy between One Line Diagram Feeder Schedule and feeder shown between CT Can and Panel LD.


PLLUMBING REVIEW COMMENTS:
Denied
Fourth Plumbing Review: Outstanding Comment that remains = 8
1). ** See Building Official letter **The #13 Ice machine on plan page P1 can't discharge to the grease interceptor. -IPC 1003.2 ** Subject to Field Inspections**
2). . ** See Building Official letter ** The M4 , #18, #31 walk-in coolers condensate on plan page P1 can't discharge to the grease system. -IPC 1003.2**Subject to Field Inspections**
3). . ** See Building Official letter **HP1, HP3, EC1 condensate on plan page P1 can't discharge to the grease system. -IPC 1003.2 ** Subject to Field Inspections**
4).OK
5). OK- Hand sink next to outdoor grill on plan page P1 needs overhang above, it can't receive rain water. -IPC 1101.3 ** Exterior sink to have cover to prevent stormwater see See Plan pages A3 & A17**
6). OK
7).. ** See Building Official letter ** Per the manufacturer website the GB-250 grease interceptor selected on plan page P6 is a hydromechanical type. The Tucson plumbing code amendments only allow 4 items to discharge to this type of grease interceptor. Update all affected plumbing pages** Subject to Field Inspections**
8).SAME- Now that the Roof primary & secondary overflow drain detail has been added to plan page A17, this design doesn't meet the requirement. The primary thru wall scupper opening in parapet wall is where the elevated secondary overflow needs to be located adjacent, not in the down spout assembly. See FPC 1106.5 **If the the primary wall scupper became blocked the current secondary drain location in the downspout assembly would not meet the intent**
9). OK
10).OK
11). OK
12). OK
13).OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
05/25/2023 Historic REQUIRES RESUBMIT Historic demo minor review documentation is required. Application and checklist found here: https://www.tucsonaz.gov/files/pdsd/Preservation/Historic_Demolition_Application_Form.pdf
05/17/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
05/10/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM07804 5201 S 12th Av
New Food Service building (3rd Review)

TRANSMITTAL DATE: May 10, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.
1. Zoning has reviewed the building plans for compliance with DP22-0124. Although it appears that the building plan matches the DP, Zoning cannot approve the building plan until the DP is approved.
2.Comment: Clarify if a separate Demo permit will be applied for, or this building permit is to include the Demo. If so the following comment is applicable.
The Pima County Assessor’s effective construction date for your building or structure is 1971. The actual construction date may be earlier.
Buildings, portions of buildings or structures that are 50 years of age or older must be architecturally documented prior to demolition. Documentation will be reviewed and approved by the Historic Preservation Office before a permit is issued.
Demolition (Historic and Older Structures) Application and General Information may be downloaded (PDF) at https://www.tucsonaz.gov/files/pdsd/Preservation/Historic_Demolition_Application_Form.pdf
Submit form and all required information through TDC Online as an attachment to the building permit, or if instructed, as part of a Special District application. Contact PDSDhistoric@tucsonaz.gov with any questions

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
04/24/2023 PDSD Application Completeness Express REVIEW COMPLETED