Permit Number: T22CM06967
Parcel: 11702191G

Address:
919 N STONE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T22CM06967
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2022 Commercial Electrical REQUIRES RESUBMIT T22CM06967

The exterior lighting inventory shown in the LUMEN DENSITY table does not correlate with the number of luminaires shown in the building lighting plans. For example; the LUMEN DENSITY table shows 89 ‘B’ type luminaires, and the building lighting plans show 100 luminaires.

Also the lumens per acre required for a Special Inspection is 100,000 not 1,000,000.

Provide compliance with the 2018 IECC for energy usage for the lighting.

Please revise the plans and resubmit.

Ref; 2018 IBC 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson/Pima County Outdoor Lighting code.
11/10/2022 PDSD Application Completeness Express REVIEW COMPLETED