Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - T22CM06967
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2022 | Commercial Electrical | REQUIRES RESUBMIT | T22CM06967 The exterior lighting inventory shown in the LUMEN DENSITY table does not correlate with the number of luminaires shown in the building lighting plans. For example; the LUMEN DENSITY table shows 89 ‘B’ type luminaires, and the building lighting plans show 100 luminaires. Also the lumens per acre required for a Special Inspection is 100,000 not 1,000,000. Provide compliance with the 2018 IECC for energy usage for the lighting. Please revise the plans and resubmit. Ref; 2018 IBC 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson/Pima County Outdoor Lighting code. |
||
| 11/10/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |