Permit Number: T22CM06956
Parcel: 133231470

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM06956
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
12/21/2022 Commercial Plumbing APPROVED RESTAMP REQUIRED
12/09/2022 External Reviewers - SAFEBuilt APPROVED Activity Number: T22CM06956
GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E2.1A ELECTRICAL POWER RENOVATION PLAN - AREA A: Two sets of office furniture share the same sets of circuits in lower left of sheet. Correct if required.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
-Each Coffee maker water connection on M3.1C Needs its own ASSE 1024 Backflow


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/07/2022 Fire New Construction APPROVED
11/07/2022 Site Zoning APPROVED
12/12/2022 Site Zoning APPROVED RESTAMP
12/09/2022 Site Engineering NOT REQUIRED RESTAMP REQUIRED
12/23/2022 Bldg Permits - Post Review REVIEW COMPLETED
11/07/2022 Commercial Plumbing REVIEW COMPLETED Water
12/12/2022 Fire New Construction REVIEW COMPLETED RESTAMP REQUIRED
11/07/2022 PDSD Application Completeness REVIEW COMPLETED
11/07/2022 Site Engineering REVIEW COMPLETED