Permit Number: T22CM06798
Parcel: 10309057A

Address:
3801 N RUNWAY DR

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - T22CM06798
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/12/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Denied
Reason:
Date Completed : 5/11/2023 7:10:15 PM
1. Structural steel, components and fasteners for the roof screen are to be protected against corrosion in accordance with AISC 360 Section B.13 as indicated in IBC 2018 Section 2203.1.

2. Designer is to coordinate venting and drainage hole requirements for HSS tube members that are galvanized using the hot-dip galvanizing process. Provide for plugs as needed.

AWS D-19.0 calls for welds on galvanized steel to be free of zinc. Field welds on galvanized parts requires the removal of the zinc coating in the area of weld. Provide zinc paint (approved by the galvanizer) and apply as required to the weld and steel area to provide protection.

1. Provide galvanized bolts on the roof platform framing connections.

2. The requirements in OSHA 1926.757 for the erection of open web steel joists are to be followed. Where steel joists are used with columns that are not framed in at least two directions with solid web structural steel members, a steel joist shall be field-bolted at the column to provide lateral stability to the column during erection. Where constructability does not allow a steel joist to be installed at the column the joists are to be stabilized on both sides of the column.

3. Provide a vertical stabilizer plate at columns for steel joist as required by OSHA 1926.757.

Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
05/03/2023 Special Inspection Certificate Review (Deferred Submittal) Express REVIEW COMPLETED