Permit Number: T22CM04809
Parcel: 140420270

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM04809
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2023 Site Engineering NOT REQUIRED
03/07/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/22/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM04809


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
Sheet A1.0 – Scope of work only shows “interior tenant improvement only” and “all site conditions to remain.” Include added exterior canopy scope in the scope of work and provide new covered area (SF).
Sheet A1.1 – Show canopy and it’s columns at exit discharge in life safety plan. The new foundations and columns may be impeding the egress. Show egress clearance widths.
Sheet A1.1 – Provide the scope of sprinkler system for new canopy. Sheet A1.0 shows fire sprinkler as deferred submittal.
Sheet A1.1 – Maximum exit access travel distance is exceeding the egress requirement table. 250’ for F-1 (warehouse) but maximum travel distances through new F-1 are 284’-11” and 258’-4”.
Sheet A1.1 – Show the common path of travels in new B and F-1 occupancy. Show common path of travel from manufacturing conference room 122 which appears to be longest path of travel.
Sheet A4.0 – Provide proposed new roof canopy and dimension. Show roofing materials and slope direction according to 2018 International Building Code (IBC) chapter 15 section 1502 and 1503.
Sheet 2.1 – 4/A2.1 shows (N) ledger per structure yet doesn’t show drainage method. Is there flashing between existing exterior finish and new canopy? (2018 IBC section 1503.2)
Sheet 2.1 – 4/A2.1 provide ceiling height of the canopy. Does it meet 2018 IBC section 1003.2 ceiling height?
Sheet 2.0 – Provide new columns and framing dimensions.
Sheet 2.0 – Identify new ledger at existing wall in roof framing plan.
Sheet 2.0 – foundation keynotes of footing is not pointing to the new foundation.


MECHANICAL REVIEW COMMENTS:
Denied
Provide ventilation calculations (IMC2018,403.3.1.1.1)


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
Canopy Revision Plumbing Review:
1). Need to address Building plan review comments related to plan pages A2.1 & A4.0 -IPC 1101.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
02/22/2023 Site Zoning REQUIRES RESUBMIT FROM: Iman Monshizadeh
PDSD Zoning Review Section
PROJECT: T22CM04809 / Commercial Addition
Plot Plan Review (Revision 1)
2650 E ELVIRA RD/ I-1 Zone
TRANSMITTAL DATE: 02/22/2022

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Addition to a commercial use like the proposed canopy requires an approved development package for the site.
A Development package is a separate submittal and must be submitted and approved prior to the approval of the commercial plans.

Information on minor changes to commercial sites can be found here:
https://www.tucsonaz.gov/pdsd/apply-permit


For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov
03/07/2023 Fire New Construction REVIEW COMPLETED
02/04/2023 PDSD Application Completeness REVIEW COMPLETED