Permit Number: T22CM04580
Parcel: 13327001C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM04580
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2023 Fire New Construction APPROVED
02/24/2023 Site Engineering APPROVED
02/22/2023 Site Zoning APPROVED
02/24/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/15/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Comment not resolved, provide the size of the water meter serving the building. [Initial comment: Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan (Utility Plan, C-04, only shows a 4” fire service line to the building). Provide the size of the water meter serving this building and the size of the backflow preventer associated with the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018.]
2. The backwater detail is missing on sheet 9 of 14.
02/07/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM04580

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
Provide documents including registered design professional stamp/seal/date. Plumbing sheets missing stamp/seal/date.
Pending complete and coordinate plans

BUILDING REVIEW COMMENTS:
DENIED
Provide documents including registered design professional stamp/seal/date. Plumbing sheets missing stamp/seal/date.
Pending complete and coordinate plans

MECHANICAL REVIEW COMMENTS:
DENIED
Provide documents including registered design professional stamp/seal/date. Plumbing sheets missing stamp/seal/date.
Pending complete and coordinate plans

ELECTRICAL REVIEW COMMENTS
DENIED
Sheet E140 – Provide light budget calculations and considerations per 2012 City of Tucson/Pima County Outdoor Lighting Code. Provide lumen calculation on plans per section 104.2.1. E140 lighting general note A. states “all exterior light fixtures to comply with local night sky ordinance” and exterior lighting fixture schedule was provided but lumen calculation on plans still missing per section 104.2.1.

PLUMBING REVIEW COMMENTS:
DENIED
Provide documents including registered design professional stamp/seal/date. Plumbing sheets missing stamp/seal/date.
Pending complete and coordinate plans.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
01/28/2023 PDSD Application Completeness REVIEW COMPLETED