Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM04198
Parcel: 11515005C

Address:
815 W GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM04198
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2023 Commercial Structural APPROVED
04/04/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/21/2023 Commercial Mechanical REQUIRES RESUBMIT The additional information added to the drawing is not sufficient to demonstrate compliance of the two paint booths to the requirements of Sections 502.7.3.1 (ventilation operation), 502.7.3.3.2 (air velocity for enclosed spray booths), and 502.7.3.6 (fan motors and belts), IMC 2018. The specifications for the paint booths should be submitted for review as well as being available for the field inspector. [Second comment: Complete mechanical details of the replacement paint booths, including all of the specifications for the two booths shall be submitted for review prior to the issuance of the permit. Reference: Section 107.2.1, IBC 2018.] [Initial comment: Item #3 in the scope of work calls for two paint booths to be replaced. Provide complete mechanical details of the replacement, including all of the specifications for the two booths. Reference: Section 107.2.1, IBC 2018.]
02/16/2023 PDSD Application Completeness Express REVIEW COMPLETED