Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T22CM03993
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/29/2022 | Commercial Electrical | APPROVED | |||
| 11/14/2022 | Commercial Structural | APPROVED | |||
| 11/14/2022 | Fire New Construction | APPROVED | |||
| 11/14/2022 | Site Zoning | APPROVED | |||
| 12/27/2022 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/27/2022 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Comment not resolved; No changes made to isometric drawing. [Initial comment: Revise the waste & vent isometric to coordinate with the waste piping design shown on the floor plan. Reference: Section 107.2.1, IBC 2018.] 2. Comment not addressed. [Initial comment: Verify if an existing grease interceptor is currently in place to prevent the discharge of fats, oil, and grease into the public sewer. If a grease interceptor is not in place, show how the public sewer is to be protected from harmful discharges. Reference: Section 1003.1, IPC 2018.] |
||
| 11/14/2022 | Commercial Mechanical | REVIEW COMPLETED | |||
| 11/14/2022 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 11/14/2022 | Site Engineering | REVIEW COMPLETED |