06/08/2023 External Reviewers - SAFEBuilt APPROVED Activity Number: T22CM02759

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/6/2023 2:48:55 PM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/2/2023 1:18:17 PM


Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditinally Approved
Reason:
Date Completed : 6/1/2023 11:28:28 PM
Approved/Subject to field approval


Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/3/2023 4:53:38 PM
Electrical Review
By: Ron Ross PE
Approved with comment.
SHEET E4.2 – PANELBOARD SCHEDULES
Comment/addendum called out for PANELBOARD L4D2 to add new 50A-3P breaker to circuit 20,22,24 and revise load and wire size per updated RCU-3.
This still seems to be 90 amp.


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/7/2023 10:17:38 PM
Plumbing Revision review = OK Subject to field inspections
06/07/2023 Site Zoning APPROVED
06/29/2023 Water - PDSD APPROVED
06/15/2023 Site Engineering NOT REQUIRED
06/29/2023 Bldg Permits - Post Review REVIEW COMPLETED
06/01/2023 Fire New Construction REVIEW COMPLETED
06/01/2023 PDSD Application Completeness REVIEW COMPLETED