Permit Number: T22CM02751
Parcel: 14101925B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM02751
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2022 Site Zoning APPROVED
11/21/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/02/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM02751

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
Plumbing Revisions Review:
1). on revised med gas plan page 3P401B Label the 6 med gas/air/vac lines in the Cath lab between the hose reels & the zone valve box the same as the OR2 room above, -IPC 106.3.1, NFPA99




If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/21/2022 Fire New Construction REVIEW COMPLETED