Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.5

Permit Number - T22CM01851
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/07/2024 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT The air balance report for the new spray booth and mixing station indicates that the makeup system for the spray booth and the mixing station exhaust are not performing as designed. The mixing station exhaust is 16% below the design airflow rate and the makeup air system is delivering 27% less makeup air to the spray booth than intended. The engineer shall review the air balance report, determine the needed corrections, and have the installation re-tested.