Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.5
Permit Number - T22CM01851
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.5
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/07/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/07/2024 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | The air balance report for the new spray booth and mixing station indicates that the makeup system for the spray booth and the mixing station exhaust are not performing as designed. The mixing station exhaust is 16% below the design airflow rate and the makeup air system is delivering 27% less makeup air to the spray booth than intended. The engineer shall review the air balance report, determine the needed corrections, and have the installation re-tested. | ||
| 08/06/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |