Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM09873
Parcel: 137055740

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - T21CM09873
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2023 Water Sterilization Report (Deferred Submittal) Express APPROVED
02/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/01/2023 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT Provide the results of the capture and containment testing of the Type I hoods. Reference: Section 507.6.1, IMC 2018.
02/07/2023 Welding Inspection (Deferred Submittal) Express REQUIRES RESUBMIT Please complete Special inspection Certificate missing signature and contractor info