Permit Number: T21CM09272
Parcel: 13002003B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - T21CM09272
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2025 Commercial Electrical Standard APPROVED
11/17/2025 Commercial Mechanical Standard APPROVED
11/17/2025 Commercial Plumbing Standard APPROVED
11/26/2025 Site Zoning Standard APPROVED Associated DP (DP17-0215) has been issued.
12/01/2025 Water - PDSD Standard APPROVED
11/13/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
11/07/2025 Site Engineering Standard NOT REQUIRED
12/02/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/17/2025 Commercial Building Standard REQUIRES RESUBMIT Ed Kulik (480) 241-0634
ekulik@willdan.com
1. Sheet A-O This plan review is for a vanilla shell only, not for occupancy.
2. Sheet A-1 Provide details for the accessible entrance. Threshold and type of door.
3. Sheet A-2 Drinking fountains need to be in alcove or have wing walls or protection for the blind ADAAG 1139A.
4. Sheet A-5 1. Provide details for the new t-bar ceiling. 2. Provide framing details for the new GWB ceiling.
5. Sheet A-5 Are all the roof trusses being replaced? If so I will need additional information, framing details, sheeting details and roofing ES report. I did not see any mention of new roof trusses in the drawing. This would be outside of the TI, more of a new structural permit.
12/02/2025 Fire New Construction Standard REVIEW COMPLETED
11/07/2025 PDSD Application Completeness Express REVIEW COMPLETED