Permit Number: T21CM06663
Parcel: 122070560

Address:
4402 E SENECA ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - T21CM06663
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2023 Site Engineering APPROVED
12/04/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/28/2023 Residential Building REQUIRES RESUBMIT T21CM06663
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

Consider using a design professional if unfamiliar with construction documentation.

Separate the submitted files with construction plans and support documents in different files. Place sheet numbers on each sheet of construction plans.

Provide a clear and concise construction plan set. Sample plans are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

1. Provide a site plan showing dimensions of buildings and utilities, R106.1.1. Show the location of all utility lines from property line to building(s) along with required alterations. Identify utility lines requiring alterations, R106.1.1.

FLOOR PLAN:

1. Provide a floor plan showing each proposed room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH. Include the identification of adjacent rooms with door or window openings in the proposed space. An altered bedroom requires code compliance for egress, R310.

STRUCTURAL PLANS:

1. Provide complete structural (roof framing) plans showing compliance with the IRC or provide an Arizona structural engineer plan set showing performance compliance, R301.1. Show all proposed repairs and alterations with 2018 IRC compliance, R301.1.
2. The proposed Patio Cover may be sited within the 3’ fire separation distance from a property line. Show compliance with R302.1 (City of Tucson Amended) by providing a wall with one-hour rated materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3, R106.1 or remove any structure closer than 3 feet to the property line.

SECTIONS - DETAILS:

1. Provide a structure section showing existing and proposed features including a foundation, sills, anchoring, framing, sheathing and insulation, R106.1, N1102.1.
2. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show with dimensions the exterior wood siding, insulation, interior sheathing, and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.
3. Clarify if ceiling/roof insulation is existing or proposed as the installation requirement has changed, R806. .

PLUMBING PLANS:

1. Provide complete plumbing plans showing any changes with 2018 IRC compliance, R301.1.
2. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe for supporting the existing and proposed dwelling units.
3. Show an individual accessible water supply shut off and water heater for the proposed dwelling building, P2903.9.1.
4. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a gas line isometric or table for showing the BTU demand and length of line to each gas appliance.

MECHANICAL PLANS:

1. Show heating/cooling facilities in all habitable rooms, R303.9.

ELECTRICAL PLANS:

1. Provide a Riser Diagram showing a sub panel and feeder size for proposed dwelling unit, NEC 225.30, E3403, Table E3704.2(1).
2. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, E3404.12.
3. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2Provide proposed wiring details showing code compliant device locations and circuit sizes. Show circuit number and size with receptacles at all walls (within 6’ of any wall location) and lighting control at each doorway both interior and exterior. Receptacle, lighting, and smoke detector circuits require arc-fault protection.
4. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity, R314.3.
5. Show the location of a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
6. Show at least one wall-switch-controlled lighting outlet providing illumination on the exterior side of each egress door having grade level access R3903.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details minimum (R-13 walls and R-30 small additions or otherwise R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better.

OUTDOOR LIGHTING CODE

Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
11/29/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T21CM06663
4402 E SENECA ST Zoning R-2

TRANSMITTAL DATE:‎November 29, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Clarify the scope of work,


2.COMMENT: Based on current aerial photos there is an addition on the rear of the house that was built sometime between 2012 and 2014. Zoning is unable to locate permit documentation, please provide permits, if no permits are available a permit will be required for the unpermitted addition. Additional comments may be forth coming.



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
11/14/2023 PDSD Application Completeness Express REVIEW COMPLETED