Permit Number: T21CM06656
Parcel: 12417147A

Address:
935 S FREMONT AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - T21CM06656
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2023 Site Engineering NOT REQUIRED
04/04/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/12/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM06656
935 S Fremont Ave. – R-2
New SFR & Detached Sleeping Quarters (2nd Review)

TRANSMITTAL: January 12, 2023

This site is located in the R-2 zone (UDC 4.7.9). Multi-family residential is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.6, .9 & .10.

This comment is still applicable.
1. As some type of land split/lot line reconfiguration has be done provide approved lot split documents with your next submittal.
-Revise the property line dimension as they appear to be incorrect.

The following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

The following comments are for the proposed SFR,

2.The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 22’-0” the required perimeter yard setback from the proposed SFR to the north and south property line is 14’-9”, proposed setback to the north & south property line is 11’-0”.

3.The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall (UDC 6.4.5.C.1.a). Based on a wall height of 22’-0” the required front street perimeter yard setback is 33’-0” proposed front street setback is 25’-0”

DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://tdc-online.tucsonaz.gov/#/
. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
01/10/2023 Fire New Construction REVIEW COMPLETED Questions:
Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
01/04/2023 PDSD Application Completeness Express REVIEW COMPLETED
02/01/2023 Residential Building REVIEW COMPLETED
04/04/2023 Zoning Modifications - DDO REVIEW COMPLETED