Permit Number: T21CM06028
Parcel: 118062830

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - T21CM06028
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/03/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL


FROM: PDSD Zoning Review

PROJECT:
T21CM06028
1862 W King Ave 1 & 2 – R-1
Duplex (2nd Review)

TRANSMITTAL: March 3, 2023

COMMENT: Resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed.

COMMENTS: The following comments are for the purpose of applying for a variance before the Board of Adjustment (UDC Section 3.10.1).

This site is located in the R-1 zone (UDC 4.7.9). Single-family residential is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.1 - .9, & .11.

1. No building plans were submitted Provide a full set of building plans that addressed the following comments.

2. Per UDC Table 4.8-2 PERMITTED USES – URBAN RESIDENTIAL ZONES, R-1 Zone a duplex is not an allowed use. A Board of Adjustment for Variance is required. If the units are separated a second permit is required.

3. Per UDC Article 4.9.7.B.3 One dwelling must be at least 25% smaller than the other dwelling. This Use Specific Standard is not met a Board of Adjustment for Variance is required.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the wall, see Unified Development Code (UDC) Article 6.4.5.b & Figure 6.4.5-A.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).
4. Based on a wall height of 13’-0” the required perimeter yard setback from the garage to the north property line is 8’-8”, proposed setback is 8’-0”. If you elect to go through the variance process the reduced perimeter yard setback can be processed through the Board of Adjustment. If the requirements of comments 1 & 2 are addressed and a variance is not required the reduced setback can be processed as a Design Development Option (DDO). DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
03/06/2023 Residential Building REVIEW COMPLETED