Permit Number: T21CM05104
Parcel: 125073370

Address:
2246 E 6TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - T21CM05104
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2023 Site Zoning APPROVED
10/12/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/02/2023 Residential Building REQUIRES RESUBMIT T21CM05104
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions, and concerns before permit approval.

GENERAL COMMENTS:

1. A special inspection request is required with the permit application for field welding (detail #15/D1), R109.2. Show manufactured assemblies without field welding or submit a privately acquired certified inspector request form for approval.

SITE PLAN:

1. Verify the accuracy of two dwelling sewer lines from property line to the building, R106.1.1.

MECHANICAL PLANS:

1. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D.

ELECTRICAL PLANS:

1. Panelboards and overcurrent protection devices shall not be in clothes closets, in bathrooms, or over the steps of a stairway, E3405.5. Show Sub Panel A outside of the master closet.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace, in a utility or laundry room, N1101.14. Add notation to plans.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
10/04/2023 Fire New Construction REVIEW COMPLETED
09/14/2023 PDSD Application Completeness Express REVIEW COMPLETED