Permit Number: T21CM04894
Parcel: 13316020X

Address:
6565 E GRANT RD

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - T21CM04894
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2023 Masonry Inspection (Deferred Submittal) Express APPROVED
11/09/2023 Site Prep Inspection (Deferred Submittal) Express APPROVED
11/02/2023 Water Sterilization Report (Deferred Submittal) Express APPROVED
11/09/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/09/2023 Concrete Installation Inspection (Deferred Submittal) Express REQUIRES RESUBMIT 7/7/2023 concrete test results in August 11,2023 report for slab on grade at front patio location indicates a test result (3028 psi average) which is less than the required concrete design strength (4000 psi) indicated by the Structural Drawings. Please have Engineer of Record evaluate and remedy this deviation form the design requirements and resubmit. NOTE: This also applies on specimen 26 test date 7/28/2023 showing strength at 3220 psi is lower than the design strength of 4000 psi
11/02/2023 PDSD Application Completeness Express REVIEW COMPLETED
11/09/2023 Post-Installed Anchor Inspection (Deferred Submittal) Express REVIEW COMPLETED