Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM02564
Parcel: 10602262A

Address:
3602 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T21CM02564
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2024 Site Engineering NOT REQUIRED
01/22/2024 Site Zoning NOT REQUIRED
02/01/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/01/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. The existing electrical line diagram shows the existing electrical service fed underground by the Utility. The new upgraded service must also be fed underground per the 2018 IBC City of Tucson adopted Amendments section 112.1.1. An underground service Waiver can be applied for if desired. The Waiver form can be downloaded from the PDSD website and submitted. Please note that all appeals to building official shall be requested through TDC-online. Appeals submitted by email will not be reviewed. .
Ref; 2018 IBC section 017.2.1, 112.1.1, 2017 NEC.
01/19/2024 PDSD Application Completeness REVIEW COMPLETED