Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - T21CM02564
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/31/2024 | Site Engineering | NOT REQUIRED | |||
01/22/2024 | Site Zoning | NOT REQUIRED | |||
02/01/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/01/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. The existing electrical line diagram shows the existing electrical service fed underground by the Utility. The new upgraded service must also be fed underground per the 2018 IBC City of Tucson adopted Amendments section 112.1.1. An underground service Waiver can be applied for if desired. The Waiver form can be downloaded from the PDSD website and submitted. Please note that all appeals to building official shall be requested through TDC-online. Appeals submitted by email will not be reviewed. . Ref; 2018 IBC section 017.2.1, 112.1.1, 2017 NEC. |
||
01/19/2024 | PDSD Application Completeness | REVIEW COMPLETED |