Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - T21CM02564
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/04/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/04/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. The previous electrical plan review comments are not addressed. As per the previous comments, the plans show the existing electrical service being fed underground by the utility. The submitted response states,” The existing feeders were already installed overhead. Electrical upgrade plans are using existing overhead feeders" The response does not correlate with the submitted plans showing existing underground service lateral. Please clarify. Also as requested. Provide documentation from the utility in writing, requesting the new electrical service to be fed with an overhead utility drop. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
02/14/2024 | PDSD Application Completeness | REVIEW COMPLETED |