Permit Number: T21CM02564
Parcel: 10602262A

Address:
3602 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3

Permit Number - T21CM02564
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/04/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The previous electrical plan review comments are not addressed.

As per the previous comments, the plans show the existing electrical service being fed underground by the utility. The submitted response states,” The existing feeders were already installed overhead. Electrical upgrade plans are using existing overhead feeders"
The response does not correlate with the submitted plans showing existing underground service lateral. Please clarify.

Also as requested. Provide documentation from the utility in writing, requesting the new electrical service to be fed with an overhead utility drop.

Ref; 2018 IBC section 107.2.1, 2017 NEC.
02/14/2024 PDSD Application Completeness REVIEW COMPLETED