Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/23/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Ref; Plan Sheet E2

1. Please clarify the conductor identification for the new feeder going to the existing service. The red shows 4-4/0 conductors, 21/2 inch conduit before the new 400 amp service disconnect. And 2 sets of the same after the disconnect.

Ref; 2018 IBC section 107.2.1, 2017 NEC