Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - T21CM02471
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/21/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
12/21/2023 | Commercial Electrical | REQUIRES RESUBMIT | Request for Overhead service does not meet either condition 1 or condition 2 for waiving the requirement for underground conductors. 1. Existing buildings on the block are served with overhead conductors or where a lot to be constructed upon is one of three or fewer abutting vacant lots making up less than 40 percent of the total acreage of the block (not including street or right-of-way) or where a vacant area is less than 60,000 square feet. 2. The installation, when compared to the use of overhead conductors, would create a hazard or not be feasible. A feasibility study will be required at the time the request for waiver is made. |
||