Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM02471
Parcel: 134130580

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - T21CM02471
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/21/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/21/2023 Commercial Electrical REQUIRES RESUBMIT Request for Overhead service does not meet either condition 1 or condition 2 for waiving the requirement for underground conductors.
1. Existing buildings on the block are served with overhead conductors or where a lot to be constructed upon is one of three or fewer abutting vacant lots making up less than 40 percent of the total acreage of the block (not including street or right-of-way) or where a vacant area is less than 60,000 square feet.
2. The installation, when compared to the use of overhead conductors, would create a hazard or not be feasible. A feasibility study will be required at the time the request for waiver is made.
10/23/2023 PDSD Application Completeness Express REVIEW COMPLETED