Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.5
Permit Number - T21CM02471
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.5
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/20/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
02/20/2024 | Commercial Electrical | REQUIRES RESUBMIT | Per this submittal response letter. It was stated,” The existing feeders were already installed overhead. Electrical upgrade plans are using existing overhead feeders”, is incorrect. See electric line diagram, plan sheet ‘E1’ shows the existing electrical service fed underground. Plan sheet ‘E2’ shows the existing electrical service feeders fed underground. Pima County, City of Tucson Maps Street view shows the existing electrical service fed underground. Per previous plan review comments, revise the electrical plan design to provide for an underground fed electrical service lateral to feed the new service. Ref; 2018 IBC section 107.2.1 and Amendments requiring underground utilities, 2017 NEC, Previous electrical plan review comments. |
||
02/14/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |