Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/04/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. The request to install an electrical service that is fed by an overhead utility drop is denied by the Building Official, Juan Garcia. See previous electrical review comment, 12-21-2023.

Please revise the electrical plans to show the electrical service fed by underground lateral.

Ref; 2018 IBC section 107.2.1, 2017 NEC