Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - T21CM02471
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/04/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
01/04/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. The request to install an electrical service that is fed by an overhead utility drop is denied by the Building Official, Juan Garcia. See previous electrical review comment, 12-21-2023. Please revise the electrical plans to show the electrical service fed by underground lateral. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
12/26/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |